Transformer stray loss simulation for tank shielding, hot spots and load-loss guarantees
The load-loss figure is guaranteed and the tank is the last part to be drawn. Surface-impedance eddy-current models and magneto-thermal coupling show where the flux goes, which shunt layout pays and how hot the wall gets, before the steel is cut.

Transformer stray loss simulation predicts where the leakage flux of the windings heats the tank, the clamps and the plates, how much it costs in load loss, and how hot the wall gets at its worst point. We build it around your existing electromagnetic and thermal solvers, with a validation record and a surrogate of stated range, so the shielding is settled before the tank drawings are released and the temperature rise test is booked.
The winding design is frozen, the load-loss guarantee is in the contract and the tank is drawn last. Then the stray flux decides whether the wall stays within its limit. In a published ABB case, the highest temperatures of the original design sat below the embossments that make room for the high-voltage bushings and exceeded the permissible limit, so those regions had to be shielded. Waiting on the answer: the tank release for fabrication, the guaranteed losses, the slot for the temperature rise test and the delivery date.
- Winding ends. At full current the windings produce a large stray flux, and the losses it causes heat the metallic parts it reaches.
- Tank wall. The wall, with the embossments that make room for the bushings, carries eddy currents. In the ABB case the high-voltage wall was the largest tank contribution to the stray loss.
- Shunts. Ferromagnetic laminated steel elements mounted on the tank wall that guide the flux leaving the winding ends and work as shields. Where they go, and how long they are, is the design variable.
- Hot spot. In the original design the highest temperatures sat below the embossments in the high-voltage wall and exceeded the permissible limit, so those regions needed shielding.
- Oil and air. The thermal model needs a convective coefficient for each surface. ABB assumed a linear oil temperature on the inner tank surfaces and a uniform air temperature over the height of the tank.
Where does the stray loss of a power transformer come from?
Load losses occur in conductors and in magnetic parts. In the windings and bus bars there are two components, resistive and eddy-current. The metallic parts exposed to the magnetic field, such as the tank and the core clamping structures, produce stray losses too, as the ABB Review paper puts it. Which of them matters most depends on the design, so the first job of the model is a loss map by part, not one stray-loss number.
The paper gives the map for one unit, a three-phase 380/110/13.8 kV autotransformer at 60 Hz, for the original shielding and for the optimised one. Shares are relative to the total stray loss of the original design, taken as 100 per cent.
| Part | Original shielding | Optimised shielding | Change |
|---|---|---|---|
| Core | 41.1 | 41.2 | Unchanged |
| Clamps | 19.1 | 18.9 | Unchanged |
| Flitch plates | 4.2 | 3.6 | Small fall |
| Tank, of which high-voltage wall | 25.6 (16.2) | 17.4 (7.8) | Wall down by 52 % |
| Shunts | 10.0 | 7.6 | Down by about 24 % |
| Total | 100.0 | 88.7 | Down by 11.3 % |
Read the table the way an engineer would. The saving is not spread evenly: the wall that was hot is the part that gains most, and the shunts' own loss falls as well. A model that returns one total would have hidden both facts.
Why is the thin skin the whole modelling problem?
The steel plates are much thicker than the depth to which the magnetic field penetrates them. To represent that small penetration with a volume mesh, a huge number of small elements is needed next to every magnetic surface, and ABB notes that this calls for computing power far beyond a workstation. The standard answer is the surface impedance boundary condition, which treats the eddy-current phenomenon as a boundary condition rather than a volume calculation, with far fewer elements.
- Steel parts in the stray field. Besides the windings and bus bars, the metallic parts exposed to the magnetic field, such as the tank and the core clamping structures, produce stray losses, as the ABB Review paper lists them.
- A thin skin. The plates are much thicker than the depth to which the magnetic field penetrates them, so the eddy currents, and the loss, sit close to the surface.
- Volume mesh across the skin. Representing that small penetration needs a huge number of small elements next to every magnetic surface, which ABB says calls for computing power far beyond a workstation.
- Surface impedance boundary condition. The phenomenon is treated as a boundary condition rather than a volume calculation, so far fewer elements are needed. ABB assigned it to the flitch plates, the tank and the clamps.
ABB assigned the boundary condition to the flitch plates, the tank and the clamps of a simplified 3D model that kept only the major components: core, windings, flitch plates, clamps, tank and the magnetic shields on the high- and low-voltage walls. Simplifying on purpose, and saying what was left out, is what makes a 3D model fast enough to be used for a sweep.
How do you find the hot spot, not only the loss?
With a coupled magneto-thermal run. The electromagnetic model gives the loss density, the thermal model turns it into temperature, and the thermal model needs a convective heat transfer coefficient for each surface. In the ABB case a linear oil temperature was assumed on the inner tank surfaces, from the lowest value at the bottom to the highest at the top, and a uniform air temperature outside. With those inputs the hot regions appeared below the embossments of the high-voltage wall, while the low-voltage wall stayed acceptable.
Those assumptions are reasonable and they are assumptions. Where the oil flow is directed by baffles, or the tank geometry is unusual, a CFD model of the oil supplies the surface temperatures and coefficients instead of assuming them. That is the point where our thermal analysis and CFD work joins the electromagnetic model, and the point we check first.
What does shield optimisation look like in practice?
ABB describes it as a process guided by experienced engineers: several shunt arrangements were calculated and compared to find the one that protected the wall best while keeping losses to a minimum. The vertical shunts were shortened and horizontal shunts were introduced to protect the regions where hot spots had been predicted. The previously observed hot spots were eliminated, and the highest temperatures moved to the vertical edges of the embossments near the top of the tank.
The authors add a remark worth keeping: a design engineer would probably never have dared to use that configuration without the insight from the 3D simulations. That is the commercial argument for the model. It lets you consider layouts that nobody would risk on judgement alone.
How close did the simulation come to the test?
At final acceptance the load losses came out within 1 per cent of the losses estimated by ABB's internal tool, and the measured stray losses, the difference between the measured load losses and the estimated winding losses, were 5 per cent above the figure calculated by FEM. The temperature rise test confirmed the tank temperatures predicted by the 3D analysis, and no excessive gases were reported in the oil, which indicates no local overheating inside the tank.
Two details explain why the numbers were that close. The simulation parameters were statistically fitted on dozens of tested units of small, medium and large power transformers, and a material library for these calculations was built from laboratory measurements. In other words the model was calibrated to tests, not only to theory. We set up the same discipline for you: your test records become the calibration, and the validation record shows how far the model is trusted.
A stray-loss model is not a test result
Where does machine learning help with transformer shielding?
In the search, not in the physics. A shield layout has a few parameters, such as shunt length, position and count, and every candidate is a 3D solve. A surrogate trained on a designed set of those solves answers in seconds inside the sampled range and passes the promising candidates back to the full model. A published framework for machine-learning-supported multi-objective optimisation reports surrogates trained on fairly small amounts of data, an evolutionary optimiser on top, the Pareto solutions checked against ground-truth simulations, and a MAPE below 5 per cent in one of its use cases. It is a different application, so we read it as a method that works, and we test it on your transformer before we rely on it.
Our surrogate-model article and validation article describe how we train and check them, and the reduced-order model page shows where they fit.
From one tank to a shielding workflow your team keeps
The return comes when your engineers run the next rating, tank shape or bushing layout through the same chain.
- Physics model. CFD and FEA set up once, as templates: geometry clean-up, mesh, solver settings and post-processing that every later run reuses.
- Validation. Mesh and time-step studies, and comparison with tests or full-scale data, so the model's uncertainty is known before it is trusted.
- Automated runs. Scripted runs over the parameters and operating conditions that matter, on your hardware or in the cloud.
- AI surrogate. A machine-learning model trained on those runs answers in seconds and says how sure it is; low-confidence questions go back to the solver.
- Decision tool. Optimisation, trade-off charts or operating guidance, in a form your engineers and operators use every day.
- Field data. Test, trial and monitoring data flow back to recalibrate the model, so it improves with every project instead of being rebuilt.
- A transformer model template: core, windings, clamps, flitch plates, tank and shunts as parameters, surface impedance on the steel parts, checked on a case with known losses.
- A calibration register: the steel data and the tested units the calibration rests on, with the spread you can expect.
- A magneto-thermal link with the oil and air boundary assumptions written down and tested, and the CFD cases that replace an assumption where it matters.
- A shield-layout sweep: shunt length, position and count against stray loss and wall temperature, with the trade-off shown.
- A validation record: your load-loss and temperature-rise tests against the model, with tolerances set before the run.
- A surrogate with a stated range and a gate back to the 3D model.
- Handover and training, so your team runs and extends it: our training and software development services.
What should you bring to a first conversation?
- The winding and core geometry, the winding-end currents and the rating, in whatever form you hold them.
- The tank and bushing layout, including embossments, and any shunts or shields you use today.
- The steel grades of tank, clamps and plates, and the calibration data behind your current loss tool.
- Test records: load losses, temperature rise and any dissolved-gas results, even from older units.
- The guarantee and temperature limit you work to, and the date the tank design has to be released.
Common questions
What is transformer stray loss?
Why use a surface impedance boundary condition?
Do magnetic shunts always help?
Can simulation replace the temperature rise test?
If a tank release, a guarantee or a temperature rise test is waiting on this, send us the winding and tank geometry, the currents, the steel grades and the test records you hold. We reply with the model chain we would set up, the validation we would run and what a surrogate could cover. Start with a conversation, or see our power transformers page. Related reading: electric motor thermal simulation and heat exchanger CFD.


